Transformers for rectifier

Transformers for rectifier (Serie: TTR)

Description Construction:

The windings of these transformers are made ​​of copper wire (double insulated with Class H insulation or double Nomex tape) or performed with aluminum tape. On request, a copper band version is possible.

The transformers are protected by a vacuum pressure impregnation with a solvent-free polyester resin and anschließßender heat treatment. The magnetic core is made from grain oriented sheets. The transformer is designed for natural air cooling. With enhanced cooling size and weight can be reduced.

Applications:

These transformers are used in power rectifiers. They are used both for isolation and voltage matching between the main network and load. Transformers with one secondary winding (Dy11) are suitable for 6-pulse rectifier and f ¨ r 12-pulse rectifier used those with two secondary windings (Dd0y11).

Product range:

Three-phase transformers (Serie: TTR)  
Primary-/Secondary Voltage 690V/690V
One secondary winding Rated power: 50...1600kVA
Two secondary windings Rated power: 70...1600kVA


Technische Daten:

Frequency 50/60Hz
Short-circuit voltage Ucc
4%
HS-Test I-II and Mass, 50Hz 3kV, 60s
Protection class IP00
Cooling normal air
Ambient temperature -5...+40°C
Installation Site <1000m above the sea (asl)
Environment-Climatic-Res. To Fire Class E1-C1-F0

Considered standards / norms

 

  • IEC EN 60076
  • IEC 60076-11
  • IEC EN 60146-1-3
  • HD 464 (VDE 0532-6)
  • CEI 14-4
  • CEI 14-32
  • CEI 22-8

Specifications:

Rectifier transformers TTR with a secondary winding 50/60Hz, Ucc=4%, Dy11
P
(kVA)
Po
(W)
Pj,115°C
(W)
dimension (mm) Mass
(kg)
Typ
L B H
50 370 1600 450 300 480 200 TTR-0050
63 380 2100 460 320 520 230 TTR-0063
80 410 2400 530 370 540 260 TTR-0080
100 600 2900 570 380 560 315 TTR-0100
125 850 3100 690 410 610 380 TTR-0125
160 950 3400 690 470 610 450 TTR-0160
200 1000 4400 720 530 680 510 TTR-0200
250 1150 5000 720 580 680 600 TTR-0250
315 1600 5600 800 550 850 750 TTR-0315
400 1800 6200 870 600 850 890 TTR-0400
500 2200 7000 870 680 850 1100 TTR-0500
1000 3500 14800 1250 760 1420 2200 TTR-1000
1600 4550 18250 1250 860 1450 3200 TTR-1600

P: Rated output at 50Hz. At 60Hz, this decreased to 90%.
Po: Power loss in the iron,
Pj,115°C: Power loss in the windings at 115 °C.

For more information, see the catalog (Italian / English)

Rectifier transformers TTR with two secondary winding 50/60Hz, Ucc=4%, Dd0y11
P
(kVA)
Po
(W)
Pj,115°C
(W)
dimension (mm) Mass
(kg)
Typ
L B H
73 550 1550 730 370 520 310 TTR12P-0073
90 600 1800 730 440 520 330 TTR12P-0090
120 650 2400 750 480 560 390 TTR12P-0120
145 750 2500 880 450 600 490 TTR12P-0145
175 800 3100 800 500 650 520 TTR12P-0175
210 900 3700 840 520 650 570 TTR12P-0210
260 1000 4300 800 590 720 670 TTR12P-0260
315 1100 5500 800 620 800 750 TTR12P-0315
390 1300 6500 850 540 900 910 TTR12P-0390
480 1800 7000 970 560 1000 1140 TTR12P-0480
610 2000 8500 970 700 1000 1380 TTR12P-0610
770 2300 9500 970 800 1000 1500 TTR12P-0770
1000 3700 14850 1250 760 1570 2400 TTR12P-1000
1600 4600 18400 1250 860 1600 3300 TTR12P-1600

P: Rated output at 50Hz. At 60Hz, this decreased to 90%.
Po: Power loss in the iron,
Pj,115°C: Power loss in the windings at 115 °C.

For more information, see the catalog (Italian / English)