Castresin 17,5kV class

General characteristics:

MV winding: Cast Resin

IEC 60076 – HD 464 S1 – DIN 42523 – CEI 14 -32

Frequency 50 Hz
Secondary Voltage at No-Load 400V
Regulation Taps On HV Side ± 2 x 2,5%
Vector Group Dyn11
Primary Insolation level 17,5 - 38 - 75 / 95kV
Secondary Insolation level 1,1 - 3kV
Ambient Temperature -25...+40°C
Environment-Climatic-Res. To Fire Class E2-C2-F1

 

Specifications:

Typ     P
(kVA)
  P0
(W)
 PCC,75°C
(W) 
 UCC
(%) 
I0
(%)  
  LWA
(dB/A)
Ohne Box(IP00)  Mit Box (IP21) 
 L
(mm)
 B
(mm)
 H
(mm)
 Masse
(kg)
 L
(mm)
 B
(mm)
 H
(mm)
 Masse
(kg)
TTRES-0100 100 400 2190 5 2,3 46 1180 645 1090 570 1030 500 1500 790
TTRES-0160 160 530 2600 6 1,7 46 1290 645 1240 700 1120 540 1650 1090
TTRES-0200 200 650 2800 6 1,3 48 1390 645 1260 860 1190 570 1720 1360
TTRES-0250 250 790 3500 6 1,7 48 1390 645 1310 940 1190 570 1770 1440
TTRES-0315 315 910 4200 6 1,5 50 1470 795 1350 1090 1240 600 1810 1630
TTRES-0400 400 1180 4610 6 1,4 51 1480 795 1420 1350 1250 600 1930 1820
TTRES-0500 500 1290 5480 6 1,3 52 1530 795 1480 1490 1280 620 1990 2100
TTRES-0630 630 1580 6700 6 1,2 54 1500 795 1580 1680 1260 610 2090 2230
TTRES-0800 800 1840 7930 6 1,0 54 1540 980 1740 2150 1290 620 2250 2640
TTRES-1000 1000 2000 9180 6 1,0 58 1570 980 1860 2450 1320 640 2420 3050
TTRES-1250 1250 2660 10100 6 1,0 60 1590 980 1930 2750 1320 640 2490 3280
TTRES-1600 1600 3350 12440 6 0,8 62 1650 980 2150 3450 1360 660 2710 3940
TTRES-2000 2000 3710 15630 6 0,7 64 1720 1230 2190 4150 1410 680 2800 4590
TTRES-2500 2500 4720 18830 6 0,8 66 1770 1230 2410 5100 1440 700 3020 5340
TTRES-3150 3150 5860 22100 6 0,7 68 2040 1270 2500 5700 1630 790 3210 7650

Description:

E.M.G. - Transformersare designed and manufactured according to CEI 14-32 and IEC 60076-11 CENELEC HD 464 and CENELEC HD 528 On request, additional standards can be applied.

The core of these transformers is made of cold rolled grain oriented steel with low losses. The surface is insulated in order to reduce eddy current losses. A special technology makes it possible to minimize the losses, and Vibaration SOUNDS. The Ns-windings are made of aluminum or copper tape (standard UNI 4507). They are insulated by coating with a special resin film. The impregnation of the windings is carried out under vacuum in order to prevent moisture absorption. This allows these transformers in high ambient temperatures, are used for heavy soiling under tropical or marine conditions.

The Ms-winding is made ​​of aluminum or copper band, surrounded by a thermal insulating material of the class F, and aligned in a special form. After heat treatment, it is cast with epoxy resin in vacuum. After the time-and temperature-controlled Polymeristion and relaxation gives a compact unit, the winding is protected by an adequate thickness of the resin. This technology allows to create MS-windings, which is protected against any kind of external accidents such as fire, humidity and condensation.

characteristic data

  • The epoxy resin used contains minerals, such as silica and alumina, and is cast in an autoclave under Vakkuum to achieve a perfect degassing with respect to the presence of air. In terms of insulation, epoxy resin is in fire class F. He has successfully passed the tests for the class E2, C2 and F1 as defined in EN IEC 60076 standards.
  • The primary windings are equipped with a 5-position bridging switch, with which an adjustment of ± 2 x 2.5% is possible. Other values ​​are available on request.
  • The ambient temperature must not exceed 40 ° C usually, and the temperature increase should I be about 100K with standard transformers in the windings.
  • E.M.G. Transformers can be performed for use in locations with ambient temperatures up to 55 ° C!
  • E.M.G. Transformers have a very low noise level of 46 dB (A) to 68 dB (A).
  • The maximum height of standard transformers is 1000 m above sea level. But it can also be manufactured transformers for higher-up locations.
  • The maxiDie transformers are equipped with Pt100 3 pcs (1 pcs in each winding Ns), connected to a temperature control unit.
  • For proper operation of the transformer a correct and natural ventilation in the room must be guaranteed. The operating conditions in function of the insulation transformer are defined by IEC IEC 60076-11 14-32.
  • For special applications where a temporary increase in performance over the nominal values ​​occurs, the use of a forced ventilation is recommended.

Tests carried out

  • Measurement and inspection of the transmission ratio and the gear group
  • Measuring the resistance of the windings
  • Measurement of no-load losses and no-load current
  • Measuring the losses of load
  • Measurement of short-circuit voltage
  • Insulation test voltage
  • Insulation test of the induced voltages
  • Measurement of Partial Discharge

Test Type (optional):

  • pulse Test
  • temperature rise

Special test (on request):

  • Measurement of noise emitted

operating conditions

In line with the environmental, climatic and fire-resistant categories the transformers can be eingestzt under the following conditions:

environment class

  • E0 No condensation on the transformer, minor soiling, installation in a clean, dry place
  • E1 Occasional condensation and little pollution
  • E2 The transformer subject to considerable condensation and / or heavy contamination

climate class

  • C1 The transformer is not suitable for operation at temperatures below -5 ° C, but can be up to -25 ° C during transportation
  • C2, the transformer can be operated, transported and stored to -25 ° C.

fire Class

  • F0, there is no fire risk, no precautions must be taken to reduce the flammability
  • F1 In case of fire, the transformer is self-extinguishing, and there are no harmful substances and / or toxic fumes emitted